Images are representations only.

SA Series Fig 9095SA Overfill Prevention Valve

Brand: Morrison Bros. Co.
The 9095SA Overfill Prevention Valve is installed at the fill port of a storage tank. Used in a pressurized tight fill application, the valve helps prevent tank overfills by closing when the liquid level reaches a pre-set warning level (90-95% full).

The valve is installed on a standard 2” NPT male connection and has a built-in bleed hole that allows the fill hose pressure to be relieved after the valve closes. This bleed hole also provides anti-siphon protection for the valve.

When installed to manufacturer requirements, the Morrison 9095SA Overfill Prevention Valve can eliminate hazardous liquid spills.

For use on clean product only. Not suitable for motor oil.
Features
Direct Fill Installations
  • Installs on tank top by threading onto a 2 inch male NPT riser
  • Installs inside 2” Morrison Model 516 or 518 tank top spill container
Remote Fill Installations
  • Valve has 2” female NPT inlet threads for installation piping to remote fill point
  • Field adjustable shutoff range between 2” to 12”
  • Full flow until shutoff point
  • Designed for fuel not requiring a drop tube
  • Integral pressure relief
show more
The 9095SA Overfill Prevention Valve is installed at the fill port of a storage tank. Used in a pressurized tight fill application, the valve helps prevent tank overfills by closing when the liquid level reaches a pre-set warning level (90-95% full).

The valve is installed on a standard 2” NPT male connection and has a built-in bleed hole that allows the fill hose pressure to be relieved after the valve closes. This bleed hole also provides anti-siphon protection for the valve.

When installed to manufacturer requirements, the Morrison 9095SA Overfill Prevention Valve can eliminate hazardous liquid spills.

For use on clean product only. Not suitable for motor oil.
Features
Direct Fill Installations
  • Installs on tank top by threading onto a 2 inch male NPT riser
  • Installs inside 2” Morrison Model 516 or 518 tank top spill container
Remote Fill Installations
  • Valve has 2” female NPT inlet threads for installation piping to remote fill point
  • Field adjustable shutoff range between 2” to 12”
  • Full flow until shutoff point
  • Designed for fuel not requiring a drop tube
  • Integral pressure relief

Specifications

Certifications & Approvals

  • ULc

Body, Piston & Lower Float Rod Material

  • Passivated Aluminum

Material of Construction

  • Float/Float Guard: Polypropylene
  • Upper Float Rod: Stainless Steel
  • Direct Fill Adaptor: Aluminum

Size

  • 2"

Viscosity

  • 300 centistokes

Flow Rate

  • 110 GPM  @ 10 psi

Operating Pressure

  • 5 to 100 psi

Applications

  • Storage Tank