Description
- Input for RTD, TC, mV, Ohm, potentiometer, mA and V
- 2-wire supply > 16.5 V to Ex zone 0
- Bipolar voltage input
- Output for current, voltage and 2 relays
- Universal supply by AC or DC
- Within a few seconds the user can program PR5116B to suit the specific application.
- By way of the front push-button the input can be calibrated to the exact span of the process. Zero drift on the process signal can be adjusted by a single press of the front buttton.
- A green front LED indicates normal operation and malfunction. A yellow LED is ON for each active output relay.
- Continuous check of vital stored data for safety reasons.
- 3-port 3.75 kVAC galvanic isolation.
Specifications
Specifications
Brand
Accuracy
- ± 0.05 %
Approvals & Certifications
- ATEX 2014/34/EU KEMA 04-ATEX-1316 X
- DNV Marine Standard F. Certificate No. 2.4
- EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
- EAC TR CU 020/2011
- EMC 2014/30/EU
- FM 3023092
- LVD 2014/35/EU
- UL 508
Calibration
- 20° to 28° C (68° to 82° F)
Environmental Protection
- IP20
Humidity
- < 95 % Relative Humidity, Non-Condensing
Load
- ≤ 600 ohms
Maximum Voltage
- 250 Vrms
Output
- 0-20 mA Signal Range
Response Time
- 250 milliseconds to 60 seconds mA/V Input (Programmable)
- 400 milliseconds to 60 seconds (0 to 90 %, 100 to 10 %)
RTD Type
- Linch R
- Ni100
- Pt100
Supply Voltage
- 19.2-300 Vdc
- 21.6-253 Vac
- 50/60 Hz
Temperature Range
- -20° to 60° C (-4° to 140° F)
Vibration
- ± 1.6 mm
- ± 4 G
Applications
Applications
- Linearized, electronic temperature measurement with RTD or TC sensor.
- Conversion of linear resistance variation to a standard analog current / voltage signal, i.e. from solenoids and butterfly valves or linear movements with attached potentiometer.
- Power supply and signal isolator for 2-wire transmitters.
- Process control with 2 potential-free relay contacts which can be configured for advanced functions.
- Galvanic separation of analog signals and measurement of floating signals.