Description
- Input for RTD, TC, mV, linear resistance, mA, and V
- 3-port 3.75 kVAC galvanic isolation
- Current and voltage output
- Universal voltage supply
- 1- and 2-channel versions
- Loop supply > 17.1 V in Ex / I.S. zone 0
- The 5114 transmitter can be configured using the PReset software and the Loop Link communications unit.
- Active or Passive current output and selectable voltage output.
- Separation of circuits in PELV/SELV installations.
- I.S. barrier for temperature sensors, potentiometers, and current / voltage signals.
- I.S. barrier with I.S. power supply for 2-wire transmitters in zone 0, 1, 2, 20, 21 and 2.
Configure
Specifications
Specifications
Brand
Accuracy
- ± 0.05 %
Approvals & Certifications
- ATEX 2014/34/EU Demko 99-ATEX-124571, II (1) GD [EEx ia] IIC
- DNV Marine Standard F. Certificate No. 2.4
- EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
- EAC TR CU 020/2011
- EMC 2014/30/EU
- LVD 2014/35/EU
- RoHS 2011/65/EU
Calibration
- 20° to 28° C (68° to 82° F)
Environmental Protection
- IP20
Humidity
- < 95 % Relative Humidity, Non-Condensing
Load
- ≤ 600 ohms
Output
- 0-20 mA Signal Range
Response Time
- 250 milliseconds to 60 seconds mA/V Input (Programmable)
- 400 milliseconds to 60 seconds Temperature Input (0 to 90 %, 100 to 10 %)
RTD Type
- Linch R
- Ni100
- Pt100
Supply Voltage
- 19.2-300 Vdc
- 21.6-253 Vac
- 50/60 Hz
Temperature Range
- -20° to 60° C (-4° to 140° F)
Vibration
- ± 1.6 mm
- ± 4 G
Applications
Applications
- Jumper selectable inputs for current/voltage or temperature.
- Programmable current (0...100 mA) and voltage (0...250 VDC) inputs.
- Linearized, electronic temperature measurement.
- Conversion of linear resistance variation e.g, from solenoids and butterfly valves or linear movements with attached potentiometer.
- 17.1 VDC loop and 2.5 VDC potentiometer supplies.
- Automatic 4- / 3-wire or programmable 2-wire cable compensation.
- Configurable sensor error detection including NAMUR NE43.