5337A 2-Wire Transmitter with HART Protocol

Brand: PR Electronics
  • RTD, TC, Ohm, and bipolar mV input
  • 2 analog inputs and 5 device variables with status available
  • HART protocol revision selectable from HART 5 or HART 7
  • Hardware assessed for use in SIL applications
  • Mounting in Safe area or Zone 2/22
Features
  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    ∙ Long Tag numbers of up to 32 characters.
    ∙ Enhanced Burst Mode and Event notification with time stamping.
    ∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    ∙ Process signal trend measurement with logs and summary data.
    ∙ Automatic event notification with time stamps.
    ∙ Command aggregation for higher communication efficiency.
  • 5337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.
show more
  • RTD, TC, Ohm, and bipolar mV input
  • 2 analog inputs and 5 device variables with status available
  • HART protocol revision selectable from HART 5 or HART 7
  • Hardware assessed for use in SIL applications
  • Mounting in Safe area or Zone 2/22
Features
  • HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
  • The HART 7 protocol offers:
    ∙ Long Tag numbers of up to 32 characters.
    ∙ Enhanced Burst Mode and Event notification with time stamping.
    ∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
    ∙ Process signal trend measurement with logs and summary data.
    ∙ Automatic event notification with time stamps.
    ∙ Command aggregation for higher communication efficiency.
  • 5337A is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
  • Continuous check of vital stored data.
  • Meeting the NAMUR NE21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337 meets NAMUR NE43 and NE89 recommendations.

Specifications

Accuracy

  • ± 0.05 %

Approvals & Certifications

  • ATEX 2014/34/EU KEMA 03-ATEX-1508 X
  • DNV Marine Standard F. Certificate No. 2.4
  • EAC TR CU 020/2011
  • EMC 2014/30/EU
  • IECEx KEM 10.0083X
  • INMETRO NCC 12.0844 X
  • SIL: Hardware Assessed for use in SIL Application

Calibration

  • 20° to 28° C (68° to 82° F)

Current

  • 0.2 mA

Environmental Protection

  • IP00
  • IP68

Humidity

  • < 95 % Relative Humidiy, Non-Condensing

Load

  • ≤ (Vsupply-8) / 0.023 ohms

Output

  • 4-20 mA Signal Range

Response Time

  • 1 to 60 seconds

RTD Type

  • Ni100
  • Ni1000
  • Ni120
  • Ni50
  • Pt100
  • Pt1000
  • Pt200
  • Pt50
  • Pt500

Supply Voltage

  • 8.0-35 Vdc

Temperature Range

  • -40° to 85° C (-40° to 185° F)

Vibration

  • ± 1.6 mm
  • ± 4 G

Applications

  • Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
  • HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
  • Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
  • Amplification of bipolar mV signals to standard 4...20 mA current signals.
  • Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.