Description
The Aquavx™ is a wireless SCADA water system for remote monitoring, control and alarm notification. It is designed for mid-sized pump and lift stations, gas compressor stations, substations, and water and wastewater treatment plants. The remote monitoring system offers fixed I/O with ten digital inputs, four analog inputs, two relay outputs and 58 Modbus RTU channels.
- Local user interface features:
- View run-times, cycles, levels, flow and totalized flow on the local display
- Control pumps, valves and other field devices
- View inflow, outflow and rain event totals
- Dynamic scrolling display allows you to choose which channels to display
- Local keypad and display for viewing status, configuration changes and more
- Alarm notifications via email, text message or voice calls:
- Excessive run times or cycles or excessive variation in pump run times or cycles
- Exceeding limits on tank levels, pressure, flow rates or motor amps
- Power fail and low battery level
- Loss of cellular or Modbus communications
- Rainfall exceeds the limit
- Local display automatically rotates any data selected for quick viewing of complete system status, including current alarms, values and signal strength
- Scheduled and/or on-demand reports for run times, total inflow and outflow, alarm history and complete audit trail
- Local relays can be automatically controlled based on preconfigured set points or conditions. They de-energize automatically when all channels have returned to normal conditions, upon the programmable timer expiring or upon local or remote request
- Peer-to-peer communication between Aquavx and Messenger units enabling system-wide controls
- Remote site viewing and management through RemoteIQ™ using mobile or desktop devices
- Powered by RemoteIQ™ Water
- For mid-sized applications
- Standard I/O includes digital, analog, relay, and Modbus channels
- Data, alarms, rosters, history and audit trails
- No networks to maintain, no engineering, and no 3rd party licensing
- Data is available 24/7 via mobile device or laptop
Specifications
Specifications
Brand
Enclosures
- NEMA 4X
- Flush/Panel mount metal enclosure
Operating Temperature
- -30° to 70° C (-22° to 158° F)
- Modem Op Temp: -40° to 85° C (-40° to 185° F)
Pulse Input Parameters
- 50 % duty cycle at a max. frequency of 5 Hz (200 msec period)
- max=25 Vdc, greater than or equal to 4 Vdc is a pulse high, less than or equal to 1.6 Vdc is a pulse low
Battery Backup
- 12 V, rechargeable sealed lead acid battery, 12-hour minimum
Power Supply
- 100-240 Vac to 13.8 Vdc, 50-60 Hz, 1.9A, DIN-rail mounted, UL-rated
Modes
- Run Mode: Average is 50 mA @ 15 Vdc. Max is 850 mA during CELL transmit
Humidity
- 0-90 % Non-Condensing @ +40 °C (+104 °F)
Serial Port
- 1 RS-485
Cellular Modem
- LTE/CATM1 dual modem utilizing AT&T or Verizon
Analog Inputs
- 4 capable of interfacing directly to 4- 20 mA, 0-5 V, 1-5 V signals. Can be flowmeters to provide flow rate and total flow
Digital Inputs
- 10 digital/pulse inputs 0-5 Hz, dry contact, open collector or closure to ground with voltages up to 25 Vdc.
Relay Outputs
- 2 relay outputs 0.5A @ 125 Vac or 30 Vdc for local control of local audio/visual devices or for controlling field devices such as pumps and valves.
Modbus I/O
- 20 Modbus RTU read coil/input status channels. Performs like physical digital inputs
- 30 Modbus RTU read holding/register channels. Performs like physical analog inputs
- 8 Modbus RTU write coil digital channels. Performs as relay outputs
Applications
Applications
- SCADA-like capabilities for mid-sized municipal, industrial and commercial water and wastewater applications