Images are representations only.

2289 Signal Calculator

Brand: PR Electronics
  • Two analog inputs
  • Multiple functions
  • Front-programmable
  • 3-digit LED display
  • Version with a Pt100 input
  • Analog output
Features
  • Programmed via the user interface which consists of a 3-digit display and 3 function keys in the front panel.
  • The A and B inputs can be programmed to receive current signals in the range 0...20 mA (eg. 4...20 mA), or voltage signals in the range 0...10 VDC.
  • Input A is a linearized Pt100 with a 3-wire connection. input B is an analog current / voltage input.
  • Digital inputs are jumper selectable NPN or PNP.
  • Analog standard current / voltage output of 0/4...20 mA / 0/2...10 VDC.
  • Both the input signals and the output signal can be inverted.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying. In environments with strong vibrations the PR 7002 can be mounted as an additional safety catch for system 2200 devices on the relay socket.
show more
  • Two analog inputs
  • Multiple functions
  • Front-programmable
  • 3-digit LED display
  • Version with a Pt100 input
  • Analog output
Features
  • Programmed via the user interface which consists of a 3-digit display and 3 function keys in the front panel.
  • The A and B inputs can be programmed to receive current signals in the range 0...20 mA (eg. 4...20 mA), or voltage signals in the range 0...10 VDC.
  • Input A is a linearized Pt100 with a 3-wire connection. input B is an analog current / voltage input.
  • Digital inputs are jumper selectable NPN or PNP.
  • Analog standard current / voltage output of 0/4...20 mA / 0/2...10 VDC.
  • Both the input signals and the output signal can be inverted.
  • Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying. In environments with strong vibrations the PR 7002 can be mounted as an additional safety catch for system 2200 devices on the relay socket.

Specifications

Approvals & Certifications

  • CE
  • EAC TR CU 020/2011
  • EMC 2014/30/EU

Consumption

  • 2.4 W

Dimensions

  • 3.17” x 1.40” x 3.33” {80.5 x 35.5 x 84.5 mm (H x W x D)} - D is without Pins

Environmental Protection

  • IP50

Humidity

  • < 95 % Relative Humidity, Non-Condensing

Input

  • 0 Vdc at 6.9 mA, Pull Down - PNP Digital Input
  • 0-10 Vdc
  • 0-20 mA
  • 200 mV - Min. Measurement Range (Span)
  • 24 Vdc at 6.9 mA, Pull Up - NPN Digital Input
  • 4 mA - Min. Measurement Range (Span)
  • Nominal 1.25 mA - RTD Sensor Current

Linearization

  • < 0.1 % of Span - Linearity Error

Load Impedance

  • ≤ 600 ohms at Current Output

Operating Time

  • 0 to 999 seconds - Differentiating & Integrating Time

Output

  • 0-20 mA
  • 20.5 mA - Current Limit
  • 5 mA - Min. Signal Range

Output Noise

  • Minimum 60 dB - Signal to Noise Ratio

Power Requirement

  • Maximum

Power Supply Effect

  • < ± 0.002 % of Span/ %V

Resistance

  • 25 ohms - Max.
  • Nominal 10 megaohms - Voltage Input Resistance
  • Nominal 50 ohms - Current Input Resistance

Resolution

  • 16-bit - Signal Dynamics, Output
  • 20-bit - Signal Dynamics, Input

Response Time

  • < 60 milliseconds

RTD Type

  • Pt100 (2289B)

Stability

  • ≤ 0.01 % of Span/100 ohms - Load

Supply Voltage

  • 19.2-28.8 Vdc
  • 2.5 Vdc ± 0.5 % at 15 mA - Auxiliary Voltage

Switch Type

  • NPN
  • PNP

Temperature Effect

  • < ± 0.01 % of Span/°C

Temperature Range

  • 20° to 28° C (68° to 82.4° F) - Calibration Temperature
  • -20° to 60° C (-4° to 140° F)

Update Time

  • 20 milliseconds

Zero Offset

  • 50 % of Selected, Max.

Applications

  • Operates as a PID controller with an analog or a Pt100 input.
  • Functions include a manual / automatic controller, an analog calculator with a scale function on both inputs, a samplehold transmitter, a peak-hold transmitter, a delay transmitter, a signal limiter, averaging of noisy signals, monitoring of a signal’s slope, or an analog multiplexer.