Description
- Universal Ex driver for solenoids, acoustic alarms and LEDs
- Extended self-diagnostics
- 1 or 2 channels
- Can be supplied separately or installed on power rail, PR 9400
- SIL 2-certified via Full Assessment
- Universal I.S. driver for the control of solenoids etc. with various I.S. data by way of three built-in I.S. barriers.
- Two hardware versions make it possible to choose either Low (35 mA) or High (60 mA) current output.
- Configuration and monitoring by way of detachable display front (PR 4500).
- Selection of direct or inverted function for each channel via PR 4500 and the possibility of reducing the output current to the hazardous area to suit the application.
- Optional monitoring of the output current to the hazardous area by way of PR 4500.
- Optional redundant supply via power rail and/or separate supply.
- 1 green and 2 yellow/red front LEDs indicate operation status and malfunction.
- 2.6 kVAC galvanic isolation between input, output and supply.
Configure
Specifications
Specifications
Brand
Approvals & Certifications
- ATEX 2014/34/EU KEMA 07-ATEX-0147 X
- CCOE P337349 / 6
- DNV Marine Standard F. Certificate No. 2.4
- EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
- EAC TR CU 020/2011
- EMC 2014/30/EU
- FM 3035277-C
- IECEx KEM 09.0001X
- INMETRO NCC 12.1306 X
- LVD 2014/35/EU
- SIL 2 Certified & Fully Assessed Accessory to IEC 61508
- UL 61010-1
Environmental Protection
- IP20
Humidity
- < 95 % Relative Humidity, Non-Condensing
Maximum Current
- 0.3 Adc
- 0.5 A AC
Maximum Voltage
- 110 Vdc
- 125 Vac
Storage Temperature
- -20° to 85° C (-4° to 185° F)
Supply Voltage
- 19.2-31.2 Vdc
Temperature Range
- -20° to 60° C (-4° to 140° F)
Vibration
- ± 0.7 G, 13.2 to 100 Hz
- ± 1 mm, 2 to 13.2 Hz
Applications
Applications
- 9203B can be mounted in the safe area or in zone 2 / Class 1, Division 2 and transmit signals to zone 0, 1, 2 and zone 20, 21, 22 including M1 mining / Class I/II/III, Div. 1, Gr. A-G.
- Driver for the control of ON / OFF solenoids, acustic alarms and LEDs mounted in safe or hazardous area.
- The 9203B is controlled by an NPN/PNP signal or a switch signal.
- Monitoring of internal error events via the individual status relay and/or a collective electronic signal via the power rail.
- The 9203B has been designed, developed and certified for use in SIL 2 applications according to the requirements of IEC 61508.
- Suitable for the use in systems up to Performance Level “d” according to ISO-13849.