Description
Features
- Input galvanically separated from output and supply
- Current or voltage input
- Signal conversion
- Current and voltage output
- 24 Vdc supply or universally supplied
- Applicable in PELV/SELV circuits
Configure
Specifications
Specifications
Brand
Accuracy
- ± 0.1 %
Approvals & Certifications
- EAC TR CU 020/2011
- EMC 2014/30/EU
- LVD 2014/35/EU
Calibration
- 20° to 28° C (68° to 82° F)
Environmental Protection
- IP50
Humidity
- < 95 % Relative Humidity, Non-Condensing
Load
- ≤ 600 ohms
Output
- 0-20 mA Signal Range
- 0-5 mA Signal Range
Response Time
- < 25 milliseconds (0 to 90 %)
Supply Voltage
- 19.2-28.8 Vdc
- 19.2-300 Vdc Universal
- 21.6-253 Vac Universal
- 50/60 Hz Universal
Temperature Range
- -20° to 60° C (-4° to 140° F)
Applications
Applications
- Factory-calibrated measurement ranges for input and outputs in the 2204 can be selected by the internal DIP-switches without the need for recalibration.
- Signal isolator for Analog current / voltage signals.
- 1 : 1 or signal conversion of Analog current /voltage signals within the ranges: 0...10 Vdc or 0...50 mA on the input and 0...20 mA and 0...10 Vdc in fixed ranges on the output.
- Analog signal conditioning with microprocessor based gain and zero offset giving a response time of less than 25 ms.