Description
- RTD, TC, Ohm, and bipolar mV input
- 2 analog inputs and 5 device variables with status available
- HART protocol revision selectable from HART 5 or HART 7
- Hardware assessed for use in SIL applications
- Mounting in hazardous gas and dust area
- HART protocol revision can be changed by user configuration to either HART 5 or HART 7 protocol.
- The HART 7 protocol offers:
∙ Long Tag numbers of up to 32 characters.
∙ Enhanced Burst Mode and Event notification with time stamping.
∙ Device variable and status mapping to any dynamic variable PV, SV, TV or QV.
∙ Process signal trend measurement with logs and summary data.
∙ Automatic event notification with time stamps.
∙ Command aggregation for higher communication efficiency. - 5337D is designed according to strict safety requirements and is therefore suitable for applications in SIL installations.
- Continuous check of vital stored data.
- Meeting the NAMUR NE 21 recommendations, the 5337 HART transmitter ensures top measurement performance in harsh EMC environments. Additionally, the 5337D meets NAMUR NE43 and NE89 recommendations.
Specifications
Specifications
Brand
Accuracy
- ± 0.05 %
Approvals & Certifications
- ATEX 2014/34/EU KEMA 03-ATEX-1537
- CSA 1125003
- DNV Marine Standard F. Certificate No. 2.4
- EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
- EAC TR CU 020/2011
- EMC 2014/30/EU
- FM 2D5A7
- IECEx KEM 10.0083X
- INMETRO NCC 12.0844 X
- SIL: Hardware Assessed for use in SIL Applications
Calibration
- 20° to 28° C (68° to 82° F)
Environmental Protection
- IP00
- IP68
Humidity
- < 95 % Relative Humidity, Non-Condensing
Load
- ≤ (Vsupply-8) / 0.023 ohms
Output
- 4-20 mA Signal Range
RTD Type
- Ni100
- Ni1000
- Ni120
- Ni50
- Pt100
- Pt1000
- Pt200
- Pt50
- Pt500
Supply Voltage
- 8.0-30 Vdc
Temperature Range
- -40° to 85° C (-40° to 185° F)
Vibration
- ± 1.6 mm
- ± 4 G
Applications
Applications
- Linearized temperature measurement with TC and RTD sensors e.g. Pt100 and Ni100.
- HART communication and 4...20 mA analog PV output for individual, difference or average temperature measurement of up to two RTD or TC input sensors.
- Conversion of linear resistance to a standard analog current signal, e.g from valves or Ohmic level sensors.
- Amplification of bipolar mV signals to standard 4...20 mA current signals.
- Up to 63 transmitters (HART 7) can be connected in a multidrop communication setup.