6331B 2-Wire Programmable Transmitter

Brand: PR Electronics
  • RTD, TC, Ohm, or mV input
  • Extremely high measurement accuracy
  • Galvanic isolation
  • Can be installed in Ex zone 0
  • 1- or 2-channel version
Features
  • Within a few seconds the user can program PR6331B to measure temperatures within all ranges defined by the norms.
  • The RTD and resistance inputs have cable compensation for 2-, 3- and 4-wire connection.
  • A limit can be programmed on the output signal.
  • Continuous check of vital stored data for safety reasons.
  • RTD, TC, Ohm, or mV input
  • Extremely high measurement accuracy
  • Galvanic isolation
  • Can be installed in Ex zone 0
  • 1- or 2-channel version
Features
  • Within a few seconds the user can program PR6331B to measure temperatures within all ranges defined by the norms.
  • The RTD and resistance inputs have cable compensation for 2-, 3- and 4-wire connection.
  • A limit can be programmed on the output signal.
  • Continuous check of vital stored data for safety reasons.

Specifications

Accuracy

  • ± 0.05 %

Approvals & Certifications

  • ATEX 2014/34/EU KEMA 06-ATEX-0115 X
  • CSA 1125003
  • EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
  • EMC 2014/30/EU
  • FM 2D5A7
  • IECEx dEK 14.0047 X

Calibration

  • 20° to 28° C (68° to 82° F)

Environmental Protection

  • IP20

Load

  • ≤ (Vsupply-7.2) / 0.023 ohms

Output

  • 4-20 mA Signal Range

Response Time

  • 1 to 60 seconds

RTD Type

  • Linch R
  • Ni100
  • Pt100

Supply Voltage

  • 7.2-30 Vdc

Temperature Range

  • -40° to 85° C (-40° to 185° F)

Applications

  • Linearized temperature measurement with Pt100...Pt1000, Ni100...Ni1000, or TC sensor.
  • Conversion of linear resistance variation to a standard analog current signal, for instance from valves or Ohmic level sensors.
  • Amplification of a bipolar mV signal to a standard 4...20 mA current signal.