Description
- Isolation and conversion of standard DC signals
- Slimline housing of 6 mm
- Response time <7 ms
- Low cost
- DIP-switch configured
- Easy configuration via DIP-switches.
- The input is protected against overvoltage and polarity error.
- Factory-calibrated measurement ranges.
- Inputs and outputs are floating and galvanically separated.
Specifications
Specifications
Brand
Accuracy
- < ± 0.2 %
Approvals & Certifications
- DNV Marine
- EAC TR CU 020/2011
- EMC 2014/30/EU
- GL V1-7-2
- LVD 2014/35/EU
- RoHS 2011/65/EU
- UL 508
Calibration
- 20° to 28° C (68° to 82° F)
Environmental Protection
- IP20
Humidity
- < 95 % Relative Humidity, Non-Condensing
Load
- ≤ 600 ohms
Output
- 0 to 23 mA Signal Range
Response Time
- < 7 milliseconds (0 to 90 %, 100 to 10 %)
Supply Voltage
- 16.8-31.2 Vdc
Temperature Range
- 0° to 70° C (32° to 158° F)
Vibration
- ± 1.6 mm
- ± 4 G
Applications
Applications
- Isolation and conversion of standard DC signals.
- Galvanic separation of analog current and voltage signals.
- Elimination of ground loops and measurement of floating signals.
- A competitive choice in terms of both price and technology for galvanic isolation of current and voltage signals to SCADA systems or PLC equipment.
- Suitable for environments with high vibration stress, e.g. ships.