Images are representations only.

5202B Pulse Isolator

Brand: PR Electronics
  • 2 channels - 2 or 4 outputs
  • Dual output
  • 5-port 3.75 kVAC galvanic isolation
  • Cable error detection
  • Universal supply by AC or DC
Features
  • PR5202B1 and 5202B2 have relays with change-over contacts or open NPN collectors available in the safe area.
  • PR5202B4 has 4 SPST relays, which are activated simultaneously two and two, available in the safe area. Each relay can be programmed to the function N.O. or N.C.
  • Inputs, outputs and supply are floating and galvanically separated.
  • 5202B is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.
show more
  • 2 channels - 2 or 4 outputs
  • Dual output
  • 5-port 3.75 kVAC galvanic isolation
  • Cable error detection
  • Universal supply by AC or DC
Features
  • PR5202B1 and 5202B2 have relays with change-over contacts or open NPN collectors available in the safe area.
  • PR5202B4 has 4 SPST relays, which are activated simultaneously two and two, available in the safe area. Each relay can be programmed to the function N.O. or N.C.
  • Inputs, outputs and supply are floating and galvanically separated.
  • 5202B is designed according to strict safety requirements and is therefore suitable for application in SIL 2 installations.

Specifications

Approvals & Certifications

  • ATEX 2014/34/EU Demko 99-ATEX-127186, II (1) GD [EEx ia] IIC
  • EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
  • EAC TR CU 020/2011
  • EMC 2014/30/EU
  • LVD 2014/35/EU
  • UL 913, UL 508

Calibration

  • 20° to 28° C (68° to 82° F)

Environmental Protection

  • IP20

Humidity

  • < 95 % Relative Humidity, Non-Condensing

Maximum Current

  • 2 A AC

Maximum Voltage

  • 250 Vrms

Supply Voltage

  • 19.2-300 Vdc
  • 21.6-253 Vac
  • 50/60 Hz

Temperature Range

  • -20° to 60° C (-4° to 140° F)

Applications

  • Pulse isolator with safety barrier for the supply of NAMUR sensors installed in the hazardous area.
  • Pulse isolator with safety barrier for the detection of mechanical contacts installed in the hazardous area.
  • One input signal can be used on two separate outputs.
  • A cable error alarm can be detected on a separate output.