Description
- Redundancy measurement with 2 input signals
- Signal calculator with the four arithmetical operations
- Duplication of the input signal
- Input for RTD, Ohm, TC, mV, mA, and V
- Universal supply by AC or DC
- Within a few seconds the user can program PR5115B to a selected application using the configuration program PReset.
- A green front LED indicates normal operation, sensor error on each sensor, and functional error.
- 5-port 3.75 kVAC galvanic isolation.
Configure
Specifications
Specifications
Brand
Accuracy
- ± 0.05 %
Approvals & Certifications
- ATEX 2014/34/EU Demko 00-ATEX-128567, II (1) GD [EEx ia] IIC
- DNV Marine Standard F. Certificate No. 2.4
- EAC Ex TR-CU 012 / 2011 RU C-DK.GB08.V.00410
- EAC TR CU 020/2011
- EMC 2014/30/EU
- LVD 2014/35/EU
Calibration
- 20° to 28° C (68° to 82° F)
Environmental Protection
- IP20
Humidity
- < 95 % Relative Humidity, Non-Condensing
Load
- ≤ 600 ohms
Output
- 0-20 mA Signal Range
Response Time
- 250 milliseconds to 60 seconds mA/V Input (Programmable)
- 400 milliseconds to 60 seconds (0 to 90 %, 100 to 10 %)
RTD Type
- Linch R
- Ni100
- Pt100
Supply Voltage
- 19.2-300 Vdc
- 21.6-253 Vac
- 50/60 Hz
Temperature Range
- -20° to 60° C (-4° to 140° F)
Vibration
- ± 1.6 mm
- ± 4 G
Applications
Applications
- Redundancy measurement of temperature by means of two sensors, where the secondary sensor takes over the measurement when a sensor error occurs on the primary sensor.
- Duplication of the input signal, e.g. from a temperature sensor or an analog process signal to two separate analog outputs.
- Signal calculator with four arithmetical operations: Addition, subtraction, multiplication and division.
- Example: Differential measurement:
(Input 1 * K1) - (Input 2 * K2) + K4 - Example: Average measurement:
(Input 1 * 0.5) + (Input 2 * 0.5) + K4 - Example: Different functions on the outputs:
Output 1 = input 1 - input 2, and Output 2 = input 1 + input 2 - I.S. safety barrier and power supply for 2-wire transmitters.