Description
- Load cell amplifier
- mV to current / voltage conversion
- Front-programmable / LED display
- Relative calibration of input span
- NPN / PNP input for external taring
- Supply for standard transducers
- A multifunction user interface consisting of three pushbuttons and a 3-digit LED display for programming.
- Front error LED.
- The analog input can be programmed for voltage in the range -40...100 mVDC.
- The digital signal can be selected as either NPN or PNP.
- Taring can either be by way of the digital input or from the front interface.
- The analog output can be programmed to current in the range 0...20 mA or voltage in the range 0...10 VDC.
- Transducer supply which can be programmed to 5...13 VDC from the front. It is up to the customer to ensure a max. load of 230 mA (e.g. 6 parallel 350 Ω load cells).
- Mounting for a standard 11-pole socket which can be adapted for DIN rail or plate use with PR’s 7023 adaptor and 7024 mounting keying.Sense input (with transducer supply used) for compensation for cable resistance to the transducer.
Specifications
Specifications
Brand
Approvals & Certifications
- CE
- EAC TR CU 020/2011
- EMC 2014/30/EU
Consumption
- 2.2 W
Dimensions
- 3.17” x 1.40” x 3.33” {80.5 x 35.5 x 84.5 mm (H x W x D)} - D is without Pins
Environmental Protection
- IP50
Humidity
- < 95 % Relative Humidity, Non-Condensing
Input
- 0 Vdc at 6.9 mA, Pull Down - PNP, Digital Input
- 10 mV - Min. Measurement Range (Span)
- 230 mA - Max.
- 24 Vdc at 6.9 mA, Pull Up - NPN, Digital Input
- -40 to 100 mV
Linearization
- < 0.1 % of Span - Linearity Error
Load Impedance
- ≤ 600 ohms at Current Output
Output
- < 23 mA - Current Limit
- 0-20 mA
- 5 mA - Min. Signal Range
Output Noise
- Minimum 60 dB - Signal to Noise Ratio
Power Requirement
- Maximum
Power Supply Effect
- < ± 0.002 % of Span/ %V - Effect of Supply Voltage Change
Resolution
- 16-bit - Signal Dynamics, Output
- 17-bit - Signal Dynamics, Input
Response Time
- 0.06 to 999 seconds
Stability
- ≤ 0.01 % of Span at 100 ohms
Supply Voltage
- 19.2-28.8 Vdc
- 5-13 Vdc - Auxiliary Voltage
Switch Type
- NPN
- PNP
Temperature Effect
- < ± 0.01 % of Span/°C
Temperature Range
- 20° to 28° C (68° to 82.4° F) - Calibration Temperature
- -20° to 60° C (-4° to 140° F)
Update Time
- 20 milliseconds
Zero Offset
- 70 % of Selected, Max.
Applications
Applications
- The 2261 converts bipolar mV signals from transducers supplied directly by the device to standard current / voltage signals.
- The 2261 is suitable for load cell application as well as other applications such as tank filling and draining, weighing with a taring function, measurement of cable tensile force, level control, signal conversion / amplification etc.